Original Smartgen HGM410N Genset Controller
Smartgen Genset Generator Controller HGM410N
Original Smartgen HGM410N Genset Controller
HGM400N series controller has two types:
HGM410N: ASM (Automatic Start Module),it controls generator to start/stop by remote signal;
HGM420N: AMF (Auto Mains Failure), updates based on HGM410N, moreover, has mains electric quantity monitoring and mains/generator automatic transfer control function, especially for automatic system composed by generator and mains.
Working Voltage | DC8. 0V to 35. 0V, Continuous Power Supply. |
Overall Consumption | <3W(Standby mode: ≤2W) |
AC voltage Input: 3 Phase 4 Wire 3 Phase 3 Wire Single phase 2 Wire 2 Phase 3 Wire | AC15V - AC360V (ph-N) AC30V - AC620V (ph-ph) AC15V - AC360V (ph-N) AC15V - AC360V (ph-N) |
Alternator Frequency | 50Hz/60 Hz |
Speed Sensor Voltage | 1.0V to 24V (RMS) |
Speed Sensor Frequency | 10,000 Hz (max) |
Start Relay Output | 5A DC28V power supply |
Auxiliary Relay Output 1 | 5A DC28V power supply |
Auxiliary Relay Output 2 | 5A DC28V power supply |
Auxiliary Relay Output 3 | 5A DC28V power supply |
Auxiliary Relay Output 4 | 5A AC250V voltage-free output |
Auxiliary Relay Output 5 | 5A AC250V voltage-free output |
Overall Dimensions | 126mm x 109mm x 44mm |
Panel Cutout | 110mm x 90mm |
CT Secondary Current | 5A (rated) |
Working Condition | Temperature: (-25~70)ºC; Humidity: (20~93)%RH |
Storage Condition | Temperature: (-25~+70)ºC |
Protection Level | IP55 Gasket |
Insulation Intensity | Apply AC2.2kV voltage between high voltage terminal and low voltage terminal; The leakage current is not more than 3mA within 1min. |
Weight | 0.26kg |
Telephone : 0086-13452987773 FAX : +86-023-61089945
Copyright©2012 HT INDUSTRIAL AUTOMATION LIMITED. All rights reserved. Website : www.genspare.com