Original Smartgen HGM9510 Genset Controller
Smartgen Genset Generator Controller HGM9510
Original Smartgen HGM9510 Genset Controller
HGM9510 Smartgen generator controller also monitors the engine, indicating the operational status and fault conditions accurately. When abnormal condition occurs, it splits bus and shuts down the genset, simultaneously the exact failure mode information is indicated by the LCD display on the front panel. SAE J1939 interface enables the controller to communicate with various ECU (ENGINE CONTROL UNIT) which fitted with J1939 interface.
CHARACTERISTICS for Smartgen HGM9510 Controller:
Working Voltage | DC8. 0V to 35. 0V, uninterruptible power supply |
Overall Consumption | <4W (Standby mode: ≤2W) |
AC Input: 3 Phase 4 Wire 3 Phase 3 Wire Single Phase 2 Wire 2 Phase 3 Wire | AC 15V - 360V (ph-N) AC 30V - 620V (ph- ph) AC 15V - 360V (ph-N) AC 15V - 360V (ph-N) |
Alternator Frequency | 50Hz/60Hz |
Speed Sensor Voltage | 1. 0 V to 24 V (RMS) |
Speed Sensor Frequency | Maximum 10,000 Hz |
Start Relay Output | 16A DC28V power supply output |
Fuel Relay Output | 16A DC28V power supply output |
Flexible Relay Output 1 | 7A DC28V power supply output |
Flexible Relay Output 2 | 7A DC28V power supply output |
Flexible Relay Output 3 | 7A DC28V power supply output |
Flexible Relay Output 4 | 7A 250VAC passive output |
Flexible Relay Output 5 | 7A 250VAC passive output |
Flexible Relay Output 6 | 7A 250VAC passive output |
Case Dimensions | 266mm x 182mm x 45mm |
Panel Cutout | 214mm x 160mm |
CT Secondary Current | Rated 5A |
Working Conditions | Temperature: (-25~+70)°C Humidity: (20~93)%RH |
Storage Conditions | Temperature:(-30~+80)°C |
Protection Level | IP55 Gasket |
Insulation Intensity | Apply AC2.2kV voltage between high voltage terminal and low voltage terminal; The leakage current is not more than 3mA within 1min. |
Weight | 0.95kg |
Telephone : 0086-13452987773 FAX : +86-023-61089945
Copyright©2012 HT INDUSTRIAL AUTOMATION LIMITED. All rights reserved. Website : www.genspare.com